Portable Appliance Testers

Catalogue

KEW 6205 - Portable Appliance Tester

Protect life and property from faulty appliances
  • Battery operated
  • PASS / FAIL result
  • Color status back light
  • 10 mA & 30 mA RCD test(Isolation transformer built in) Memory function up to 999 data
  • Printer output
  • Complies to AS / NZS 3760

Range

× 5, × 1, × 1/2, AUTO RAMP(mA)

Rated Voltage

100V±10% 200V-10%?+32% 400V±10% 50/60Hz

Test current

15/30/50/100mA ,15/30/50/100/200/500mA, 15/30/50/100/200/500mA,

Measuring range

Testing time 0ms?200ms, Testing time 0ms?2000ms, Testing time 0ms?2000ms, 40% - 110% of l?n (goes up by 5%) Testing time 300ms × 15steps

Accuracy (Trip Time)

1%rdg±3dgt, 1%rdg±3dgt, 1%rdg±3dgt, Test Current at each step -4%?+4%

Measuring range

80V?450V 50/60Hz

Accuracy

2%rdg±4dgt

Applicable standards

IEC 61010-1 Pollution degree2 CAT III 300V / CAT II 400V, IEC 61010-031 IEC 61557-1, 6 IEC 60529 (IP54)

Display

1999 counts (3 1/2digits), Large LCD

Operating temperature & humidity range

0ºC - 40ºC, relative humidity 85% (no condensation)

Storage temperature & humidity range

-20ºC - 60ºC, relative humidity 85% (no condensation)

Insulation resistance

50M? or more / 1000V (between electrical circuit and enclosure)

Sleep Function

(1)Automatically enters Sleep mode in 3 minutes after the last switch operation (current consumption 75µA). This function doesn't work at voltage measurements. To exit from the Sleep mode, set the Function switch to OFF position once, and re-set it to the Range at which a measurement to be conducted. (2) Backlight turns off in 1 minute after it lights up.

Power source

DC 12V / R6(AA)(1.5V) × 8

Dimensions

167(L)×186(W)×89(D)mm

Weight

Approx. 965g (including batteries)

Possible number of Measurements

1200 times or more (measure every 30 seconds at ×1/2 Range, l?n=100mA)

Included Accessories

7128A (Test leads) 7129A (Test lead with alligator clip) 8017 (Long pin) × 2 Cord case, 9121 (Shoulder strap), Instruction manual, R6(AA) × 8
related products
;